ChipFind - документация

Электронный компонент: EM24DINAV93XR2X

Скачать:  PDF   ZIP
Specifications are subject to change without notice EM24DINDS210706
1
Class 1 (kWh) according to EN62053-21
Class 2 (kvarh) according to EN62053-23
Accuracy 0.5 RDG (current/voltage)
Energy analyzer
Instantaneous variables readout: 4 DGT
Energies/gas/water readout: 7+1 DGT
System variables: VLL, VLN, Admd, VA, VAdmd, VAdmd
max, W, Wdmd, Wdmd max, var, PF, Hz, Phase-sequence.
Single phase variables: VLL, VLN, A, VA, W, var, PF
Energy measurements: total and partial kWh and kvarh
or based on 4 different tariffs; single phase measure-
ments
Gas, cold water, hot water, kWh remote heating mea-
surements
Hour counter (6+2 DGT)
TRMS measurements of distorted sine waves (volt-
ages/currents)
Self power supply (AV0-AV9 inputs)
Auxiliary power supply (AV5-AV6)
3 digital inputs for tariff selection, DMD synch or
gas/water (hot-cold) and remote heating metering (on
request)
2 digital outputs for pulses or for alarms or as a mix of
them (on request)
Product Description
Three-phase energy analyzer
with built-in configuration
joystick and LCD data dis-
playing; particularly indicat-
ed for active and reactive
energy metering and for cost
allocation. Housing for DIN-
rail mounting with IP50
(front) protection degree.
Direct connection up to 64A
and by means of external
current and potential trans-
Energy Management
Energy Analyzer
Type EM24 DIN
Dimensions: 4-DIN modules
Protection degree (front): IP50
RS485 serial output (on request) (MODBUS-RTU), iFIX
SCADA compatibility
Application adaptable display and programming
procedure (Easyprog function)
Easy connections management
MID "annex MI-003" (Measuring Instruments Directive)
compliant
formers. Moreover the
meter can be provided with
digital outputs that can be
either for pulse proportional
to the active and reactive
energy being measured or
for alarm outputs. In alter-
native the RS485 communi-
cation port and 3 digital
inputs are available as an
option.
Model
Range code
System
Power supply
Output
Option
How to order EM24 DIN AV5 3 X O2 X
Type Selection
Range codes
AV5:
AV5: 400V
LL
AC - 1/5
(10)A (CT connection) (*)
AV6:
120V
LN
/208V
LL
AC -
1/5(10)A (VT/PT and CT
connections) (*)
AV0:
120V
LN
/208V
LL
AC -10(64)A
(Direct connection) (**)
AV9:
400V
LL
AC - 10(64)A (*)
(Direct connection)
Options
X:
none (*)
P:
PTB approval (**)
System
1:
1-phase., 2-wire;
3-phase, 3-wire,
balanced load (**)
3:
balanced and
unbalanced load:
3-phase, 4-wire;
3-phase, 3-wire;
2-phase, 3-wire;
1-phase, 2-wire (*)
Output
XX:
none (*)
O2:
dual open collector
type (dual pulse or one
pulse + one alarm or
dual alarm) (*)
R2:
dual relay type (func-
tions as per "O2") (**)
XS:
RS485 port (**)
IS:
3 digital inputs for tariff
selection or Gas /
water / remote heating
metering plus RS485
port (*)
DP:
Dupline port (**)
Power supply
X:
Self power supply
See "Power supply
specifications" (*)
L:
18 to 60VAC/DC (48
to 62Hz) (**)
D:
115/230 VAC (48 to
62Hz) (*)
Note: "L" and "D" power
supplies only for AV5
and AV6 inputs; "X"
power supply only
for AV0 and AV9
inputs.
(*) as standard.
(**) on request.
2
Specifications are subject to change without notice EM24DINDS210706
EM24 DIN
Rated inputs
System type: 3
Current type
Galvanic insulation by
means of built-in CT's (AV5
and AV6 models)
Current range (by CT)
AV5 and AV6: 1/5(10)A
Voltage
AV5: 400VLL;
Voltage by VT/PT
AV6: 120/208VLL
Current range (direct)
AV0: 10(64)A; AV9: 10(64)A
Voltage
AV0: 208 VLL AC
AV9: 400 VLL AC
Accuracy (Display + RS485)
Ib: see below, Un: see below
(@25C 5C, R.H.
60%, 48 to 62Hz)
AV5 model
In: 5A, Imax: 10A; Un: 160
to 480VLN (277 to 830VLL)
AV6 model
In: 5A, Imax: 10A; Un: 40 to
144VLN (70 to 250VLL)
AV0 model
Ib: 10A, Imax: 64A; Un: 96
to 144VLN (166 to 250VLL)
AV9 model
Ib: 10A, Imax: 64A; Un: 184
to 276VLN (318 to 480VLL)
Current
AV5, AV6 models
From 0.002In to 0.2In:
(0.5% RDG +3DGT)
From 0.2In to Imax:
(0.5% RDG +1DGT).
AV0, AV9 models
From 0.004Ib to 0.2Ib:
(0.5% RDG +3DGT)
From 0.2Ib to Imax:
(0.5% RDG +1DGT).
Phase-neutral voltage
In the range Un: (0,5%
RDG +1DGT)
Phase-phase voltage
In the range Un: (1% RDG
+1DGT)
Frequency
0.1Hz (45 to 65Hz)
Active and Apparent power
(1%RDG +2DGT)
Power Factor
[0.001+1%(1.000 - "PF
RDG")]
Reactive power
(2%RDG +2DGT)
Energies
Class 1 according to
EN62053-21 and MID
Annex MI-003 Class B
Class 2 according to
EN62053-23
AV5, AV6 models
In: 5A, Imax: 10A;
0.1 In: 0.5A,
Start up current: 10mA
AV0, AV9 models
Ib: 10A, Imax: 64A;
0.1 Ib: 1,0A,
Start up current: 40mA
Energy additional errors
Influence quantities
According to EN62053-21,
EN62053-23
Temperature drift
200ppm/C
Sampling rate
1600 samples/s @ 50Hz
1900 samples/s @ 60Hz
Display
3 lines (1 x 8 DGT; 2 x 4
DGT)
Type
LCD, h 7mm
Instantaneous variables read-out
4 DGT
Energies
Imported Total/Partial/
Tariff: 7+1DGT or 8DGT;
Exported Total/Partial/
Tariff: 6+1DGT or 7DGT
(with "-" sign).
Overload status
EEEE indication when the
value being measured is
exceeding the "Continuous
inputs overload" (maximum
measurement capacity)
Max. and Min. indication
Max. instantaneous vari-
ables: 9999; energies:
9 999 999.9 or 99 999999.
Min. instantaneous vari-
ables: 0; energies 0.0 or 0
LEDs
Red LED (Energy con-
sumption),
1000 imp./kWh/kvarh
Max frequency: 16Hz
according to EN62052-11
Measurements
See "List of the variables
that can be connected to:"
Method
TRMS measurements of
distorted wave forms.
Coupling type
Direct for AV0 and AV9
models. By means of
external CT's for AV5 and
AV6
Crest factor
Ib 10A
4 (91A max. peak)
In 5A
3 (15A max. peak)
Current Overloads
Continuous
1/5(10) A: 10A, @ 50Hz
10(64) A: 64A, @ 50Hz
For 500ms
1/5(10) A: 200A, @ 50Hz
For 10ms
10(64) A: 1920A max, @ 50Hz
Voltage Overloads
Continuous
1.2 Un
For 500ms
2 Un
Input impedance
208VL-L (AV6)
>1600K
208VL-L (AV0)
Refer to "Power Consump-
tion"
400VL-L (AV5)
>1600K
400VL-L (AV9)
Refer to "Power Consump-
tion"
1/5(10) A (AV5-AV6)
< 0.3VA
10(64) A (AV0-AV9)
< 4VA
Frequency
45 to 65 Hz
Joystick
For variable selection and
programming of the instru-
ment working parameters
Input specifications
Specifications are subject to change without notice EM24DINDS210706
3
EM24 DIN
Note
The meters equipped with
the relay outputs ("AV0"
and "AV9" models with
"R2" option) work even if
VL1 is missing (VL3, VL2
and neutral have to be
available)
RS485
Type Multidrop,
bidirectional
(static and dynamic vari-
ables)
Connections 2-wire
Max. distance 1200m
Termination directly on the
instrument
Addresses
247, selectable by means
of the front joystick
Protocol MODBUS/JBUS
(RTU)
Data (bidirectional)
Dynamic (reading only)
System and phase vari-
ables: see table "List of
variables..."
Static (writing only)
All the configuration
parameters.
Data format
1 start bit, 8 data bit, no
parity,1 stop bit
Baud-rate
4800, 9600 bits/s
Driver input capability
1/5 unit load
Maximum 160 transceivers
on the same bus.
Insulation
By means of optocouplers,
4000 VRMS output to
measuring input.
4000 VRMS output to
supply input
Note:
The meters equipped with
the communication port
("AV0" and "AV9" models
with "XS" and "IS" options)
work even if VL1 is missing
(VL3, VL2 and neutral have
to be available)
Dupline
Bus
Full Dupline compatibility
Addresses
128, selectable by means
of the front joystick
Variables
Total kWh, total kvarh.
W, Wdmd, Wdmd max
Digital outputs
Pulse type
Number of outputs
Up to 2, independent.
Programmable from 0.01 to
1000 pulses per
kWh/kvarh.
Type
Outputs connectable to the
energy meters (Wh/varh)
Pulse duration
100ms < 120msec (ON),
120ms (OFF), according
to EN62052-31
Alarm type
Number of outputs
Up to 2, independent
Alarm modes
Up alarm, down alarm (see
the table "List of the
variables that can be
connected to")
Set-point adjustment
From 0 to 100% of the dis-
play scale
Hysteresis
From 0 to full scale
On-time delay
0 to 255s
Output status
Selectable; normally
de-energized and normally
energized
Min. response time
700ms, filters excluded.
Set-point on-time delay: "0 s"
Note
The 2 digital outputs can
also work as a dual pulse
output, dual alarm output,
one pulse output and one
alarm output.
Static output
Purpose
For pulse output or alarm
output
Signal V
ON
1.2 VDC/ max. 100 mA
V
OFF
30 VDC max.
Insulation
By means of optocuplers,
4000 VRMS output to
measuring inputs,
4000 VRMS output to
power supply input.
Relay output
Purpose
For alarm output or pulse
output
Type
Reed Relay, SPST type
AC 1-5A @ 250VAC
DC 12-5A @ 24VDC
AC 15-1.5A @ 250VAC
DC 13-1.5A @ 24VDC
Insulation
4000 VRMS output to
measuring input.
4000 VRMS output to
supply input.
Output specifications
4
Specifications are subject to change without notice EM24DINDS210706
EM24 DIN
Password
Numeric code of max. 4
digits; 2 protection levels
of the programming data:
1st level
Password "0", no protec-
tion;
2nd level
Password from 1 to 9999,
all data are protected
System selection
System 3-Ph.n unbalanced load
3-phase (4-wire);
3-phase (3-wire).
System 3-Ph.1 (only AV5 and AV6)
balanced load
3-phase (3-wire) one cur-
rent and 3-phase to phase
voltage measurements.
3-phase (4-wire) one cur-
rent and 3-phase to neutral
voltage measurements.
3-phase (2-wire) one cur-
rent and 1-phase (L1) to
neutral voltage measure-
ment.
System 2-Ph
2-phase (3-wire).
System 1-Ph
1-phase (2-wire).
Transformer ratio
VT (PT)
1.0 to 999.9 / 1000 to 9999
/ 10.00k to 60.00k (only
AV6)
CT
1.0 to 999.9 / 1000 to 6000
(only AV5 and AV6). The
maximum power being
measured cannot exceed
210 MW (calculated as
maximum input voltage
and current, see the
"Accuracy" paragraph
before. The maximum VT
by CT ratio is 48.600). For
MID complaint applications
the maximum power being
measured is 25MW.
Filter
Operating range
0 to 100% of the input dis-
play scale
Filtering coefficient
1 to 32
Filter action
Measurements, serial output
(fundamental variables: V, A, W
and their derived ones).
Displaying
Up to 3 variables per page
See Display pages 8
different set of variables
available (see Display
pages ) according to the
application being selected
Reset
By means of the front
joystick:
- dmd and max. dmd;
- total energies and
gas/water: kWh, kvarh;
- partial energies and
tariffs: kWh, kvarh
Easy connection function
AV9-AV0 models
Automatic phase sequence
detection with current and
voltage synchronisation.
AV5-AV6-AV9-AV0 models
For all the display selec-
tions, both energy and
power measurements are
independent from the cur-
rent direction. The dis-
played energy is always
"imported" with the only
exception of "F" and "H"
types (see "display pages"
table). For those latter
selections the energies can
be either "imported" or
"exported" depending on
the current direction.
Software functions
Number of inputs
3
Input frequency
20Hz max, duty cycle 50%
Prescaler adjustment
From 0,1 to 100,0 m
3
/
pulse
Contact measuring voltage
5VDC +/- 5%
Contact measuring current
10mA max
Input impedance
680
Contact resistance
100
, closed contact
500k
, open contact
Working modes
Selectable:
total and partial energy
meters (kWh and kvarh)
without digital inputs;
total and partial energy
meters (kWh and kvarh)
managed by time periods
(t1-t2-t3-t4), W dmd syn-
chronisation (the synchro-
nisation is made every time
the tariff changes) and
GAS (m
3
) or WATER (hot-
cold m
3
) or remote heating
(kWh) meters;
Digital input specifications
total and partial energy
meters (kWh and kvarh)
managed by time periods
(t1-t2), W dmd synchroni-
sation (the synchronisation
is made independently
from the tariff selection)
and GAS (m
3
) or WATER
(hot-cold m
3
) or remote
heating (kWh) meters;
total energy (kWh, kvarh)
and GAS, WATER (hot-cold
m
3
) and remote heating
meters (3 choices only).
Note
The energy metering is
only made by means of the
analogue inputs.
Insulation
By means of optocouplers,
4000 VRMS digital inputs
to measuring inputs.
4000 VRMS digital inputs
to supply input.
Specifications are subject to change without notice EM24DINDS210706
5
EM24 DIN
Self supplied version
AV9-AV0 models "O2" and
"DP" options only: -20%
+15%, 48-62Hz "R2", "XS"
and "IS" options only:
-15% +10%, 48-62Hz
Note
The instruments provided
with "IS" and "R2" options
work only if all the voltage
inputs are connected (3-
phase and neutral). If a 1-
phase connection has to
be performed, the L1, L2
and L3 voltage inputs have
to be short circuited.
The instrument provided
with "O2" option, working
in a 3-phase system with
neutral may work also if
one or two phases are
missing.
Auxiliary power supply
AV5-AV6 modules:
L: 18 to 60VAC/DC;
D: 115VAC/230VAC
(48 to 62Hz)
Power consumption
AV9-AV0 models
20VA/1W
AV9-AV0 models
(IS option only)
12VA/2W
AV5-AV6 models
2VA/2W
Power supply specifications
Radio frequency suppression According to CISPR 22
Standard compliance
Safety
IEC60664, IEC61010-1
EN60664, EN61010-1
EN62052-11
Metrology EN62053-21,
EN62053-23.
MID "annex MI-003"
Pulse output
DIN43864, IEC62053-31
Approvals
CE, PTB (Revenue
Approvals)
Connections
Screw-type
Cable cross-section area
AV0-AV9 models
Max. 16 mm
2
(measuring
inputs);
Min. 2.5 mm
2
(measuring
inputs)
Other inputs: 1.5 mm
2
Min./Max. screws tighten-
ing torque: 1.7 Nm / 3 Nm
Cable cross-section area
AV5-AV6 models
Max. 1.5 mm
2
Housing DIN
Dimensions (WxHxD)
71 x 90 x 64.5 mm
Material Nylon
PA66,
self-extinguishing: UL 94 V-0
Mounting
DIN-rail
Protection degree
Front
IP50
Screw terminals
IP20
Weight
Approx. 400 g (packing
included)
Operating temperature
-25C to +55C (13F to
131F) (R.H. from 0 to 90%
non-condensing @ 40C)
according to EN62053-21
and EN62053-23
Storage temperature
-30C to +70C (22F to
140F) (R.H. < 90% non-
condensing @ 40C)
according to EN62053-21
and EN62053-23
Installation category
Cat. III (IEC60664,
EN60664)
Insulation (for 1 minute)
4000 VRMS between mea-
suring inputs and power
supply.
4000 VRMS between power
supply and RS485/digital
output
Dielectric strength
4000 VRMS for 1 minute
Noise rejection CMRR
100 dB, 48 to 62 Hz
EMC
According to EN62052-11
Electrostatic discharges
15kV air discharge;
Immunity to irradiated
Test with current: 10V/m
from 80 to 2000MHz;
Electromagnetic fields
Test without any current:
30V/m from 80 to
2000MHz;
Burst
On current and voltage
measuring inputs circuit:
4kV
Immunity to conducted
disturbances
10V/m from 150KHz to
80MHz
Surge
On current and voltage
measuring inputs circuit:
4kV; on "L" auxiliary power
supply input: 1kV;
General specifications