ChipFind - документация

Электронный компонент: RN2F48V50

Скачать:  PDF   ZIP
Specifications are subject to change without notice (30.09.2005)
1
AC solid state relay, 1- and 2-poles
Analog switching for resistive loads (heating)
4-20 mA or 0-10 V controls
Rated operational current: 1-pole : 30A and 50A
2-pole : 2 x15A and 2 x 25A
Rated operational voltage up to 480 VAC
LED-indication for normal operation and alarm status
IP 20 protection
DIN-rail mountable
Product Description
Ordering Key
RN 1 F 40 V 30
The analog switching relay pro-
vides a number of full cycles,
evenly distributed over a fixed
period, depending of the con-
trol input. The input of 4-20 mA
or 0-10 VDC respectively,
corresponds to zero and full
output within a period of 1.28 s
@ 50 Hz (1.07 s @ 60 Hz). This
principle makes the transfer
characteristics fully linear. The
principle operates with zero
switching, thus ensuring a
reduced level of radiated and
wire conducted noise. The 2-
pole type has alarm LED indi-
cation by loss of master
phase. The analogue Full
Cycle Switching is not recom-
mended for light control due
to light-flickering.
Solid State Relay
Number of poles
Switching type
Rated operational voltage
Control signal
Rated operational current
Solid State Relays
Analog Full Cycle Switching
Type RN.F
Type Selection, 1-Pole
Rated
Control
Control
Rated operational current
operational voltage
input
supply
30 A
50 A
120 VAC
4-20 mA
7-10 VDC
RN 1F12I30
RN 1F12I50
0-10 VDC
12-32 VDC, 24 VAC
RN 1F12V30
RN 1F12V50
230 VAC
4-20 mA
7-10 VDC
RN 1F23I30
RN 1F23I50
0-10 VDC
12-32 VDC, 24 VAC
RN 1F23V30
RN 1F23V50
480 VAC
4-20 mA
7-10 VDC
RN 1F48I30
RN 1F48I50
0-10 VDC
12-32 VDC, 24 VAC
RN 1F48V30
RN 1F48V50
Type Selection, 2-Pole
Rated
Control
Control
Rated operational current
operational voltage
input
supply
30 A Total (2 x 15A)
50 A Total (2 x 25A)
120 VAC
4-20 mA
7-10 VDC
RN 2F12I30
RN 2F12I50
0-10 VDC
12-32 VDC, 24 VAC
RN 2F12V30
RN 2F12V50
230 VAC
4-20 mA
7-10 VDC
RN 2F23I30
RN 2F23I50
0-10 VDC
12-32 VDC, 24 VAC
RN 2F23V30
RN 2F23V50
480 VAC
4-20 mA
7-10 VDC
RN 2F48I30
RN 2F48I50
0-10 VDC
12-32 VDC, 24 VAC
RN 2F48V30
RN 2F48V50
2
Specifications are subject to change without notice (30.09.2005)
Thermal Specifications
RN.F..30
RN.F..50
Operational temperature
-20 to +70C (-4 to +158F)
-20 to +70C (-4 to +158F)
Storage temperature
-20 to +100C (-4 to +212F)
-20 to +100C (-4 to +212F)
Junction temperature
< 125C (257F)
< 125C (257F)
R
th
junction to ambient (AC load)
2.8 K/W
1.7 K/W
General Specifications
RN.F12...
RN.F23...
RN.F48...
Operational voltage range
85 to 140 VAC
85 to 265 VAC
190 to 530 VAC
Non-rep. peak voltage
800 V
p
800 V
p
1000 V
p
Varistor voltage
275 VAC
275 VAC
510 VAC
Zero voltage turn-on
< 10 V
< 10 V
< 20 V
Operational frequency range
45 to 65 Hz
45 to 65 Hz
45 to 65 Hz
Power factor at rated voltage
0.9
0.9
0.9
Average output power
0 to 100%
0 to 100%
0 to 100%
Output power resolution
1/64 of 100%
1/64 of 100%
1/64 of 100%
Approvals
UL, cUL, CSA
UL, cUL, CSA
UL, cUL, CSA
CE-marking
Yes
Yes
Yes
Norms fulfilled
EN 60947-1 Low-voltage switchgear and control gear. Part 1- General Rules.
EN 61000-6-1 Generic Immunity Standard. Residential, Commercial & Light Industry Environment
EN 61000-6-2 Generic Immunity Standard. Industrial Environment
Output Specifications
RN.F..30
RN.F..50
Rated operational current
RN1F..
AC51
@Ta=30C
30 A
50 A
"
@Ta=40C
30 A
50 A
"
@Ta=50C
23 A
38 A
"
@Ta=60C
20 A
30 A
RN2F..
AC51
@Ta=30C
30 A total sum (2 x 15A)
50 A total sum (2 x 25A)
"
@Ta=40C
30 A total sum (2 x 15A)
50 A total sum (2 x 25A)
"
@Ta=50C
23 A total sum (2 x 11.5A)
38 A total sum (2 x 19A)
"
@Ta=60C
20 A total sum (2 x 10A)
30 A total sum (2 x 15A)
Zero crossing detection
Yes
Yes
Min. operational current (per pole)
500 mA
500 mA
Rep. overload current t=1 s
(Tj init.=25C)
55 A (rms)
125 A (rms)
Non-rep. surge current t=10 ms
(Tj init.=25C)
< 300 A
p
< 580 A
p
Off-state leakage current,
@ rated voltage and frequency
(Tj.=125C, max.)
< 6 mA
< 6 mA
I
2
t for fusing t=1 to 10 ms
450 A
2
s
1680 A
2
s
Critical dV/dt off-state
500 V/s
500 V/s
RN 1F
Input Specifications
RN.F..I..
Current controlled input
Control current range
4 - 20 mA
Allowable input current
50 mA
Reverse polarity protected
Yes
Voltage drop
10 VDC @ 20 mA
RN.F..V..
Voltage controlled input
Supply voltage range
21 - 27 VAC, 12 - 32 VDC
Supply current
30 mA @ 24 VAC/32 VDC
Control voltage range
0 - 10 V
Control input current
0.1 mA @ 10 VDC
Specifications are subject to change without notice (30.09.2005)
3
Insulation
Rated impulse withstand voltage
Input to output
4000 V
imp
Rated impulse withstand voltage
Output to heatsink
4000 V
imp
Dimensions
Dimensions
(H x W x D)
RN..30
120 x 45 x 110 mm
RN..50
120 x 90 x 110 mm
Housing Specifications
Mounting
DIN-rail 35 mm
Weight with RHN1
470 g
Weight with RHN2
780 g
Housing material
Noryl SEI, GFN1, Black
LED window material
PC Lexan 141R
Base plate
Aluminium, nickel plated
Potting compound
Polyurethane, Casco Nobel
Terminals
Screw with captive wire clamp
Control terminals nominal
4 mm
2
or 2 x 2.5 mm
2
AWG 12 or 2 x AWG 14
Min.
0.5 mm
2
, AWG 20
Mounting torque max.
0.6 Nm
Power terminals nominal
10 mm
2
or 2 x 6 mm
2
AWG 6 or 2 x AWG 10
Min.
1 mm
2
, AWG 16
Mounting torque max.
2.0 Nm
Heatsink compound used
Electrolube HTS
Environment Specifications
Humidity max.
95%, no condensation
RN 1F
Dimensions
4
120
45
33,7
103
71,6
37
30
20
70
60
4
120
93
72
45
89
103
71,6
37
20
70
30
60
Note: all dimensions in mm
Wiring Diagrams
L
1
A
1
A
2
T
1
4 - 20 mA

+
Current Control
_
L
1
A
1
A
2
T
1
A
3
A
4
0 - 10 VDC

+
Voltage Control
_
Control
Supply
L
1
A
1
A
2
T
1
4 - 20 mA

+
Current Control
_
L
1
A
1
A
2
T
1
A
3
A
4
0 - 10 VDC

+
Voltage Control
_
Control
Supply
L
2
L
2
T
2
T
2
Single-pole relay
Double-pole relay
Note: all dimensions in mm
RN..30
RN..50
4
Specifications are subject to change without notice (30.09.2005)
VAC / VDC
A
2
X
X
+
_
A
3
A
4
L
1
T
1
C/V
L
2
T
2
X
X
A
1
Functional Diagrams
Applications
Terminal Layout
1-pole RN..
2-pole RN..
L
1
A
1
A
2
A
1
L
2
L
1
T
1
A
3
T
1
A
4
A
3
T
2
RN 1F
A
2
A
4
Double pole relay in 3-phase application
Star and delta application (Economy Switching only)
L
1
L
2
L
3
2-pole current controlled input
Master
Slave (2-pole version)
Single and double pole relay application
Line-Neutral
L
1
L
2
N
VAC/VDC (A
3
, A
4
only used for voltage control)
control
signal