ChipFind - документация

Электронный компонент: S104156924

Скачать:  PDF   ZIP
Specifications are subject to change without notice (11.05.99)
1
Plug
Output
Time range
Supply:
24 VAC/DC & 115-230 VAC
Circular
SPDT
0.1 s - 10 h
S 104 156 924
Timers
Time ranges: 0.1 s to 10 h
4 selectable functions: - Delay on operate
- Interval timer
- Interval timer, delay on release
- Recycler
Easy time and function setting
External adjustable time setting
Automatic and manual start functions
Repeatability:
0.2%
Output: 5 A SPDT relay
Plug-in module, S-housing
LED-indication for relay and power supply ON
24 VAC/DC and 115 to 230 VAC power supply
Cadmium-free contacts
Timer in accordance with IEC 61812-1
Product Description
Multi-function, multi-voltage
timer with 6 selectable time
ranges from 0.1 s up to 10 h
for standard 11-pin circular
sockets. Used as a general
timer in industrial applications
where remote time adjust-
ment is necessary.
Ordering Key
Housing
Type/function
Output
Power supply
Type Selection
Time Specifications
Time ranges
Selectable by DIP-switch
0.1 - 1 s
1 - 10 s
0.1 - 1 m
1 - 10 m
0.1 - 1
h
1 - 10
h
Setting accuracy
5%
Repeatability
0.2%
Time variation
Within rated power supply
0.05%/V
and ambient temperature
0.2%/C
Time setting
Linear remote potentiometer
10 k
20%, 0.25 W
Max. length of potentiometer cable 3 m
Rated insulation voltage
None
Reset
Manual reset of time and/or relay Interconnect pins 5 & 2
Pulse duration
100 ms
Power supply interruption
200 ms
Output Specifications
Output
SPDT relay
Rated insulation voltage
250 VAC (rms) (cont./elect.)
Contact ratings (AgNi)
(micro gap)
(IEC 60947-5-1/IEC 60337)
Resistive loads
AC 1
5 A/250 VAC
DC 1
5 A/24 VDC
Small inductive loads AC 15
5 A/250 VAC
DC 13
2 A/24 VDC
Mechanical life
10 x 10
6
operations
Electrical life
AC 1
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Insulation voltage
Rated insulation voltage
2.0 kVAC (rms) (cont./elect.)
Rated impulse withstand volt. 4 kV (1.2/50 s) (cont./elect.)
(IEC 60664)
Multi-function
Type S 104
S 104 156 924
Power supply DC connection Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through pins 2 & 10
924
24 VDC, -15 to +15%
(interconnect pins 6 & 10)
(pin 2 positive)
Voltage interruption
40 ms
Rated insulation voltage
None
Rated impulse withstand volt. 1 kV (1.2/50 s) (pin 2 & 6)
Rated operational current
AC supply
50 mA @ 230 VAC
25 mA @ 115 VAC
35 mA @ 24 VAC
DC supply
20 mA @ 24 VDC
Supply Specifications
Power supply AC connection Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through pins 2 & 10
115-230 VAC, -15 to +15%
50/60 Hz, -5/+5 Hz
or pins 2 & 10
24 VAC, -15 to +15%
(interconnect pins 6 & 10)
50/60 Hz, -5/+5 Hz
Voltage interruption
40 ms
Rated insulation voltage
None
Rated impulse withstand volt. 4 kV (1.2/50 s) (pin 2 & 10)
2
Specifications are subject to change without notice (11.05.99)
Operation Diagram
Function 2. Relay ON
Function 3. Relay ON
Function 1. Relay ON
Reset (interconnect 5 & 2)
Power supply
S 104
Mode of Operation
Function 1
Delay on operate
The time period starts when
pins 5 and 2 are interconnect-
ed. At the end of the set delay
the relay will operate and will
not release until pins 5 and 2
are interconnected again, or
power supply is interrupted.
The time period will autostart
when pins 5 and 2 are con-
stant connected.
Function 2
Interval timer
The relay operates and the
time period starts when pins 5
and 2 are interconnected. At
the end of the set delay the
relay releases. The relay will
operate again when pins 5
and 2 are interconnected. For
autostart connect pins 5 and
2 before power supply is ap-
plied. A recovery period of 200
ms should be allowed before
reapplying power supply.
Function 3
Interval timer
Delay on release
Power supply must be con-
stantly applied. When inter-
connecting pins 5 and 2 the
relay will operate. When pins
5 and 2 are disconnected, the
time period starts, and when
the set time period has expired,
A1
N
115-230V
24V (-)
16
18
3
1
6
5
4
2
15
A2
A3
115-230V
L
24V (+)
S
Y1
10
8
11
9
@24V (-)
Wiring Diagram
Function 4. Relay ON
Accessories
Socket
S 411
Hold down spring
HF
Mounting rack
SM 13
Socket cover
BB 4
Potentiometer kit
PK 10K
General Specifications
Power ON delay
200 ms
Power OFF delay
200 ms
Indication for
Power supply ON
LED, green
(flashing during timing)
Output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
2 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
100 g
Approvals
CE
EMC
Electromagnetic
Compatibility
Immunity
Acc. to EN 50082-2
Emission
Acc. to EN 50081-1
Timer specifications
Acc. to IEC 61812-1
Recycler
OFF-time period first
When pins 5 and 2 are inter-
connected the recycler func-
tion starts with OFF-time first.
Note:
The external potentiometer
must be connected before the
S-system will operate. Cable
length to the potentiometer
must be below 3 m.
Warning:
Pins 8, 9 and 11 for connection
of potentiometer have the same
potential as the supply voltage.
the relay releases. If pins 5
and 2 are connected again
before the time period has
expired, the time is reset and
the time period restarts when
the interconnection between
pins 5 and 2 is interrupted.
Function 4
Recycler
ON-time period first
When power supply is applied
the relay operates and the time
period starts. At the end of the
first set time period, the relay
releases for the set time period.
This sequence continues with
equal ON- and OFF-time periods
until power supply is interrupted.
A
B
A
B
A
B
A
B
Function and Time Setting
DIP-switch selector
x 1
sec.
min.
hrs.
x 0.1
A
B
Shown example:
min. x 0.1, function 2
ON OFF