Level Sensors
Level control for solid, fluid, or granulated
substances
SV 150/250: Max./min. control of DISCHARGING
SV 160/260: Max./min. control of CHARGING
Factory-set sensitivity
For capacitive sensors VR.. and VRY..
10 A SPDT or 8 A DPDT output relay
LED-indication: SV 150/250: Power supply and relay ON
SV 160/260: Relay ON
AC or DC power supply
Product Description
Ordering Key
SV 150 024
Level control relays for
capacitive sensors, types VR
and VRY. The relays can con-
trol one or two levels of
charging (SV 160/260) or dis-
charging (SV 150/250).
Housing
Output
Power supply
Type Selection
Plug
Output
Function
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
Supply: 24 VDC
Circular
SPDT
Discharging
SV 150 024
SV 150 115
SV 150 230
SV 150 724
DPDT
Discharging
SV 250 024
SV 250 115
SV 250 230
SV 250 724
SPDT
Charging
SV 160 024
SV 160 115
SV 160 230
SV 160 724
DPDT
Charging
SV 260 024
SV 260 115
SV 260 230
SV 260 724
Amplifier, Capacitive
Types SV 150/250, SV 160/260
Input Specifications
Sensitivity
depends on sensor type
and material
Sensor voltage
max. 24 VDC
terminal 6 is negative
Sensor current
Activated
min. 15 mA, max. 20 mA
Not activated
max. < 5 mA
Sensor short-circuit current
max. 45 mA
Supply Specifications
General Specifications
Power supply AC-types
Overvoltage cat. II (IEC 60664)
Rated operational voltage
through pin 2 & 10
230
230 VAC 15%
115
115 VAC 15%
024
24 VAC 15%
Rated insulation voltage
2.0 kVAC (rms)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
(line/neutral)
Power supply DC-types
Installation cat. II (IEC 60664)
Rated operational voltage 724
24 VDC 15% (pin 2 pos.)
Rated insulation voltage
None
Rated transient protection volt. 800 V (1.2/50 s)
Indication for
Output ON
LED, red
Power supply
LED, green
(only SV 150/250)
Environment
Degree of protection
IP 20 B
Pollution degree
3 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Approvals
UL, CSA
CE-marking
Yes
SV 160/260
SV 150/250
2
Specifications are subject to change without notice (25.06.99)
Mode of Operation
Max. and/or min. control of
solid, fluid or granulated
substances, e.g. sand,
gravel, sugar or chemicals.
SV 150/250: Relay control of
DISCHARGING
SV 160/260: Relay control of
CHARGING
Example 1
The diagram shows the level
control connected as max.
and min. control, i.e. registra-
tion of 2 levels during charg-
ing (discharging).
The relay releases (operates)
when the max. sensor is in
contact with the substance,
provided that the min. sensor
is immersed. The relay oper-
ates (releases) when the min.
sensor is no longer in contact
with the substance.
Example 1
The diagram shows the level
control connected as max. or
min. control, i.e. registration
of 1 level during charging (dis-
charging).
The relay releases (operates)
when the sensor is in contact
with the substance.
SV 150/250, SV 160/260
Output Specifications
SV150/SV160
SV250/SV260
Output
SPDT relay
DPDT relay
Rated insulation voltage
250 VAC (rms)
250 VAC (rms)
(cont./elec.)
(Cont./elec., cont./cont.)
Contact ratings (Ag-CdO)
(micro gap)
(micro gap)
Resistive loads
AC 1
10 A/250 VAC (2500 VAC)
8 A/250 VAC (200 VA)
DC 1
1 A/250 VAC (250 W)
0,4 A/250 VDC (100 W)
or
10 A/25 VDC (250 W)
4 A/25 VDC (100 W)
Small inductive loads
AC 15
2.5 A/230 VAC
2.5 A/230 VAC
DC 13
5 A/24 VDC
5 A/24 VDC
Mechanical life
5 x 10
7
operations
5 x 10
7
operations
Electrical life
10
5
operations
10
5
operations
Operation frequency
7200 operations/h
7200 operations/h
Insulation voltages
Rated insulation voltage
AC
2.0 kVAC (rms)
2.0 kVAC (rms)
(cont./elect.)
(cont./elect.)
DC
None
None
Rated impulse withstand voltage
AC
4 kV (1.2/50 s)
4 kV (1.2/50 s)
(cont./elect.) (IEC 60664)
(cont./elect.) (IEC 60664)
DC
800 V
800 V
Wiring Diagrams
Example 1: Two levels max./min.
Example 2: One level
Power Supply
Power Supply
Max. or Min.
Min.
Max.
Specifications are subject to change without notice (25.06.99)
3
Operation Diagrams
Power supply
Max.
Min.
Relay on
Accessories
Sensors: Types VR and VRY
Bases
Hold down spring
Base covers
Front mounting bezel
Optical: VP
Capacitive: DR, EC
SV 150/250, SV 160/260
Example 1
SV 150/250 DISCHARGING
Example 1
SV 160/260 CHARGING
Power supply
Max./Min.
Relay on
Power supply
Max./Min.
Relay on
Example 2
Example 2
Power supply
Max.
Min.
Relay on