ChipFind - документация

Электронный компонент: SV210230

Скачать:  PDF   ZIP
Specifications are subject to change without notice (25.06.99)
1
Level Sensors
Level control for conductive liquids
Max.-min. control of DISCHARGING
SV 110/210: Fixed sensitivity
SV 115/225: Adjustable sensitivity
10 A SPDT or 8 A DPDT output relay
LED-indications: Power supply and relay ON
AC or DC power supply
Product Description
Ordering Key
SV 110 024
Level control relay for con-
ductive liquids which can
control two levels of dis-
charging. Usable for one
level detection with pin 5
and 7 short-circuited.
Housing
Output
Power supply
Type Selection
Plug
Output
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
Supply: 24 VDC
Circular
SPDT
SV 110 024
SV 110 115
SV 110 230
SV 110 724
DPDT
SV 210 024
SV 210 115
SV 210 230
SV 210 724
SPDT
SV 115 024
SV 115 115
SV 115 230
SV 115 724
DPDT
SV 215 024
SV 215 115
SV 215 230
SV 215 724
Amplifier, Conductive
Types SV 110/210, SV 115/215 (Discharging)
Input Specifications
Level probe supply
Max. 24 VAC
Level probe current
Max. 2.5 mA
Sensitivity
SV110/SV210
ON
From 22 to 29 k
OFF
From 32 to 40 k
SV115/SV215
ON
From 2-6 to 20-30 k
(adj.)
OFF (AC)
From 3-13 to 30-40 k
(adj.)
OFF (DC)
From 3-9 to 42-52 k
(adj.)
Supply Specifications
General Specifications
Power supply
AC types
Overvoltage cat. II (IEC 60664)
Rated operational voltage
through pins 2 and 10 230
230 VAC 15%
50/60 Hz, -5/+5 Hz
115
115 VAC 15%
50/60 Hz, -5/+5 Hz
024
24 VAC 15%
50/60 Hz, -5/+5 Hz
Rated insulation voltage
250 VAC (rms)
Rated impulse withstand volt.
4 kV (1.2/50 s) (line/neutral)
Power supply
DC types
Overvoltage cat. II (IEC 60664)
Rated operational voltage
724
24 VDC 15% (pin 2 pos.)
Rated insulation voltage
None
Rated impulse withstand volt.
800 V (1.2/50 s)
Indication for
Power supply ON
LED, green
Output ON
LED, red (724 only red)
Environment
Degree of protection
IP 20 B
Pollution degree
3 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Approvals
UL, CSA
CE-marking
Yes
SV 110/210
SV 115/215
2
Specifications are subject to change without notice (25.06.99)
Mode of Operation
Max. and min. control of
discharging.
Example 1
The diagram shows the level
control connected as max.
and min. control, i.e. detec-
tion of 2 levels. The relay
operates when the max. elec-
trode is in contact with the li-
quid. The relay releases when
the min. electrode is no
longer in contact with the li-
quid. By use of a container of
a conductive material (pin 7)
can be connected to the con-
tainer. If the container is made
of a non-conductive material,
an additional electrode is
needed, indicated by the dot-
ted line in the diagram.
Example 2
If only one level is required,
pins 5 and 7 must be inter-
connected to select either
max. or min. control.
Wiring Diagrams
SV 1xx/SV 2xx, two levels
Example 1
SV 110/210, SV 115/215
SV 1xx/SV 2xx, one level
Example 2
Output Specifications
SV110/SV115
SV210/SV215
Output
SPDT relay
DPDT relay
Rated insulation voltage
250 VAC (rms)
250 VAC (rms)
(cont./elec.)
(Cont./elec., cont./cont.)
Contact ratings (Ag-CdO)
(micro gap)
(micro gap)
Resistive loads
AC 1
10 A/250 VAC (2500 VAC)
8 A/250 VAC (200 VA)
DC 1
1 A/250 VAC (250 W)
0,4 A/250 VDC (100 W)
or
10 A/25 VDC (250 W)
4 A/25 VDC (100 W)
Small inductive loads
AC 15
2.5 A/230 VAC
2.5 A/230 VAC
DC 13
5 A/24 VDC
5 A/24 VDC
Mechanical life
5 x 10
7
operations
5 x 10
7
operations
Electrical life
10
5
operations
10
5
operations
Operation frequency
7200 operations/h
7200 operations/h
Insulation voltages
Rated insulation voltage
AC
2.0 kVAC (rms)
2.0 kVAC (rms)
(cont./elect.)
(cont./elect.)
DC
None
None
Rated impulse withstand voltage
AC
4 kV (1.2/50 s)
4 kV (1.2/50 s)
(cont./elect.) (IEC 60664)
(cont./elect.) (IEC 60664)
DC
800 V
800 V
Operation Diagram
Power supply
Max. electrode in liquid
Min. electrode in liq.
Relay on
Accessories
Conductive level probe:
1 or 2 electrodes
VH..., VPC..., VPP...
VN..., VNY..., VNI...
VT..., VTI..., VS...
Power Supply
Power Supply
Min.
Max.
Max. or Min.